Wet-bulb temperature

Temperature in °C · supported range: −20 to 50.

Enter 5–99%, or exactly 100% for saturated air.

Wet-bulb temperature · Tw

— °C
Estimated temperature

Temperature difference · T − Tw

— °C
Dry-bulb minus wet-bulb temperature
Calculation method & limitations

Uses Stull’s approximation at standard sea-level pressure: 101.325 kPa. The published range is −20 to 50°C and 5–99% relative humidity, with limitations when conditions are both cold and dry.

Tw ≈ T × atan(0.151977 × √(RH + 8.313659)) + atan(T + RH) − atan(RH − 1.676331) + 0.00391838 × RH3/2 × atan(0.023101 × RH) − 4.686035

T and Tw are in °C. RH is entered as a percentage: 94.2, not 0.942. Both a decimal point and a decimal comma are accepted.

At exactly 100% RH, Tw = T and the temperature difference is zero. Values between 99% and 100% are outside this approximation’s published range and are not calculated here.

If the approximation produces Tw above T, no result is shown. A pressure-dependent psychrometric calculation is needed for those conditions.

Source: Roland Stull (2011)